May
28, 2003
Central Sprinkler Company Update Voluntary Recall To Replace O-Ring Fire Sprinklers
Central
Sprinkler Company, an affiliate of Tyco Fire Products LP, of Lansdale, Pa., are
announcing a modification to the voluntary replacement program announced on July
19, 2001. The company is replacing 35 million Central fire sprinklers that have
O-ring seals. The program also includes a limited number of O-ring models sold
by Gem Sprinkler Company and Star Sprinkler, Inc. totaling about 167,000
sprinkler heads. Under the original recall program, consumers were required to
use Central contractors. Now, after notifying Central in advance and completing
certain forms, consumers also can hire their own contractors and be reimbursed
for all or some of the labor charges.
Central initiated the voluntary replacement program in 2001 because it
discovered the performance of these O-ring sprinklers can degrade over time.
These sprinkler heads can corrode or minerals, salts and other contaminants in
water can affect the rubber O-ring seals. These factors could cause the
sprinkler heads not to activate in a fire. Central is providing newer fire
sprinklers that do not use O-ring seals.
Central is providing free of charge replacement sprinkler heads and the labor
needed to replace the sprinklers. As before, Central will arrange for the
installation by using either its own Central Field Service crews or by
contracting with professional sprinkler contractors. Now, consumers can arrange
to have the free replacement sprinklers installed themselves rather than
waiting for Central to arrange for installation. Subject to certain conditions,
including advance notice to Central, verification of the replacements and
return of the removed sprinklers, Central will provide either full or partial
reimbursement for labor charges.
Building and homeowners should check their fire sprinklers immediately to
see if they are part of this voluntary replacement program. For more
information on how to identify sprinklers subject to this program and to learn
how to participate in this program, call the Notice Packet Request Line at
1-800-871-3492 24 hours a day, 7 days a week or access the program's web site
at http://www.sprinklerreplacement.com/VRP/enterVRP.php3